Effectiveness of 1-bromo-3-chloro-5,5-dimethylhydantoin against Legionella pneumophila in a cooling tower.
Cooling towers are considered to be man-made amplifiers of Legionella spp. Thus, the proper maintenance and choice of biocides is important. The only biocidal measure that has thus far been shown to be effective in field tests is the judicious use of chlorination. Perturbation studies with 1-bromo-3-chloro-5, 5-dimethylhydantoin (Bromicide; Great Lakes Chemical Corp., West Lafayette, Ind.) (BCD) were conducted on an industrial cooling tower shown to contain Legionella pneumophila. At the concentrations recommended by the manufacturer, neither the density nor the activity of L. pneumophila was affected. At comcentrations greater than 2.0 ppm (2.0 micorgram/ml) free of residual, BCD was not effective in reducing L. pneumophila to source water concentrations, nor was it effective in reducing the 2-p-iodophenyl-3-p-nitrophenyl-5-phenyl tetrazolium chloride activity of the bacterium in situ. The data indicate that at concentrations up to 2.0 ppm, BCD is not effective in these tower studies.[1]References
- Effectiveness of 1-bromo-3-chloro-5,5-dimethylhydantoin against Legionella pneumophila in a cooling tower. Fliermans, C.B., Harvey, R.S. Appl. Environ. Microbiol. (1984) [Pubmed]
Annotations and hyperlinks in this abstract are from individual authors of WikiGenes or automatically generated by the WikiGenes Data Mining Engine. The abstract is from MEDLINE®/PubMed®, a database of the U.S. National Library of Medicine.About WikiGenesOpen Access LicencePrivacy PolicyTerms of Useapsburg